Data Sheets & SDSs

Technical data sheets and SDSs for all the Dynalene heat transfer fluids have been listed below. Engineering guides are also available for certain fluids. Please click on the links to obtain them. If you need more information regarding any Dynalene heat transfer fluid then call us at 1.877.244.5525 or email your requirements to info@dynalene.com.

Type here to search

Order Kit & Test

Pre-labeled 100 mL Sampling Kit (with SDS) from Dynalene Labs

Kit Includes: Leak-proof 100 mL sample bottle, branded return mailer box with absorbent pouch, SDS & chain-of-custody card, and prepaid return shipping label. Placeholder Image and Text

Great! We’ve received your request.

Dynalene Labs · Whitehall, PA

Example Advanced Fluid Analysis Report

Fluid: Dynalene PG (35% Vol)  |  Sample Volume: 100 mL  |  Status: ACTION REQUIRED — Remediation Recommended
Diagnostic Category Analytes Measured (ppm) Sample Results (ppm) Assessment
Corrosion Products (ICP-OES) Fe, Al, Cu, Pb, Sn, Ag, Zn Fe: 18.4 ppm, Cu: 6.2 ppm, Al/Pb/Sn/Ag/Zn: < 0.5 ppm Elevated Fe & Cu
Contaminants (IC / ICP) Ca, Mg, Si, B, Mo, Na, SO₄²⁻, Cl⁻, NO₃⁻ Cl⁻: 92 ppm, Ca: 28 ppm, Mg: 9 ppm, SO₄²⁻: 34 ppm Hard Make-Up Water Ingress
Glycol Breakdown Products (IC) Glycolate, Formate, Acetate, Oxalate Glycolate: 310 ppm, Formate: 85 ppm, Acetate: 22 ppm, Oxalate: < 5 ppm Moderate Thermal Oxidation

Dynalene Engineering Recommendation: Elevated chloride (92 ppm) and hardness ions indicate un-deionized make-up water top-offs, while glycolate/formate organic acids have begun consuming reserve alkalinity and mobilizing iron/copper. Proactive Fix: Install an in-line / side-stream Dynalene CRS Series Ion Exchange unit with DYS 5 µm Filtration to strip chlorides and organic acids, then dose with custom Dynalene PG Inhibitor Booster.

Dynalene Labs · Whitehall, PA

Example Basic Fluid Analysis Report

Fluid: Dynalene PG (40% Vol)  |  Sample Volume: 100 mL  |  Status: PASS — Healthy
Test Parameter ASTM / Method Sample Result Target Specification Assessment
Appearance Visual Inspection Clear, fluorescent yellow, free of sediment Clear, free of suspended solids Normal
Fluid Concentration (Density & Refractive Index) ASTM D3321 / D5931 39.5% Volume PG (Freeze Pt: -21°C / -6°F) 40.0% ± 2.0% Volume Within Spec
pH Level (25°C) ASTM D1287 9.1 8.5 – 10.0 Optimal
Electrical Conductivity Conductivity Meter 2.84 mS/cm 2.50 – 3.50 mS/cm Normal
Inhibitor Package Health (Reserve Alkalinity) ASTM D1121 11.8 mL (96% active inhibitor remaining) ≥ 9.0 mL Passivated

Dynalene Engineering Recommendation: Fluid concentration, pH, conductivity, and corrosion inhibitor levels are all within optimal specification. No glycol adjustment or re-inhibition required at this time. Next routine Basic Testing checkup recommended in 6 months (semi-annual schedule)

Pre-Labeled 100 mL Sampling Kit: Includes a leak-proof 100 mL sample bottle, branded return mailer box with absorbent pouch, SDS & chain-of-custody card, and prepaid return shipping label.

Talk to an Engineer

Discuss test results, inhibitor boosters & in-line hardware

Great! We’ve received your request.

Program Inquiry

Dynalene Promise, Dynalene Protect & On-Demand Testing

Great! We’ve received your request.

Program Inquiry

Dynalene Promise, Dynalene Protect & On-Demand Testing

Great! We’ve received your request.

Submit Fluid Sample

Send your coolant sample to Dynalene Labs

Great! We’ve received your request.

⚙️ Talk to an Engineer

Custom solutions for your application

Great! We’ve received your request.

⚡ Quick Quote

We'll respond as soon as possible

Great! We’ve received your request.